Measuring pipe wall thickness with corrosion

How much wall a pipe has left, without shutting it down and from one side. How not to miss a pit and how to compare one inspection with the next.

Short answer

  • Ultrasound measures the remaining wall thickness of a pipe from the outside and from one side, with the plant in service.
  • Corrosion isn't uniform: pitting is missed if you take a single reading per point. You have to scan each area and keep the minimum.
  • Measuring at the same points every time, with their position recorded, shows how much wall is lost from one inspection to the next.
B-Scan and corrosion analyser: the QS5

As well as measuring, the QS5 draws the thickness profile in real time as you slide the transducer (B-Scan) and warns you when the back wall is irregular, the typical sign of corrosion or pitting. And in its DLE version, it measures through paint.

What to look for: general loss and pitting

General corrosion

The wall thins more or less evenly. Spread spot readings detect it well, and what matters is the trend: how much wall is lost per year and how much margin remains to the minimum allowable thickness.

Pitting

Very localised losses, a few millimetres across, that can go through the wall while the rest of the pipe looks sound. They are the most dangerous and the easiest to miss: a reading two centimetres from a pit gives the nominal thickness.

That is why, on a corroded pipe, a measuring point is not a reading: it is an area you scan with the transducer, keeping the lowest value.

Cross-section of a pipe wall with a pit on the inner face: two spot readings either side give the nominal thickness and the pit between them is not seen; scanning the area finds it scan the areanominalnominalpit
A spot reading only measures under the transducer face: two centimetres from a pit it gives the nominal thickness. That is why each point is scanned with the transducer, keeping the lowest value.

How to measure, step by step

  1. Prepare the surface. Remove loose rust and scale where the transducer will sit. If the pipe is painted and the paint is well bonded, you don't need to remove it with the QS5 DLE echo-echo mode (see the guide measuring through paint).
  2. Calibrate the zero and set the velocity of the pipe material (see the ultrasonic velocity guide). If the pipe is hot, calibrate at its temperature.
  3. Define a grid of points on the pipe, marked and numbered, especially at elbows, tees, reducers, low points and supports, which is where corrosion concentrates most.
  4. At each point, scan the area by sliding and slightly rotating the transducer, and keep the lowest reading. The QS5 holds it on screen together with the highest.
  5. Store each reading with its position (grid row and column) to compare it with the next inspection.
dmq QS3 thickness gauge measuring on a pipe
Measuring wall thickness on a pipe: the transducer sits on couplant and is moved over the area looking for the minimum.

Problem 1: a pit between two readings

The symptom: the pipe passes inspection with every reading above the minimum and, months later, a leak appears.

Why it happens: a spot reading only measures under the transducer face. A pit two centimetres away isn't seen.

How it is solved: by scanning each area instead of measuring a point, and keeping the lowest value.

With the QS5: it holds the minimum (and maximum) on screen as you slide the transducer, so there is no need to watch the reading. And its B-Scan draws the thickness profile in real time: a pit shows up as a dip in the graph.

Transducer sliding over a pipe wall with a pit and, below, the B-Scan thickness profile: the pit shows up as a dip and the minimum value is marked slideB-Scanminimum
As you slide the transducer, the QS5 B-Scan draws the thickness profile: the pit shows up as a dip in the graph, and the gauge holds the minimum on screen.

Problem 2: corrosion or poor coupling?

The symptom: a low or unstable reading in a specific area. It may be a pit… or a lack of couplant.

Why it happens: an irregular back wall scatters the sound and weakens the echo, just like poor coupling.

How it is solved: by looking at the echo quality as well as the number, and repeating with proper coupling before drawing conclusions (see couplant gel).

With the QS5: the energy bar shows the strength of the received echo, and the material condition analyser warns when the back wall is irregular, the typical sign of corrosion or pitting. It is a prompt to measure that area in more detail, not a final result.

Problem 3: a point below the minimum allowable that goes unnoticed

The symptom: after hundreds of readings, nobody notices the one below the pipe's minimum thickness.

How it is solved: with an automatic warning at the moment of measuring.

With the QS5: alarms for minimum thickness (the allowable one for that pipe) and for material fault, with sound, light and on-screen warning.

Problem 4: being unable to compare with the last inspection

The symptom: there are readings from a year ago, but nobody knows exactly which points, and wall loss per year can't be calculated.

How it is solved: by always measuring on the same grid of points and storing each reading with its position.

With the QS5: up to 32,000 readings in files organised in rows and columns, with date, time and statistics, transferred to PC with dmq DataCenter.

The QS3 also holds the minimum value and stores readings, but has no B-Scan or analyser: it is the option for thickness checks without corrosion mapping.

Which transducer to use

Which transducer to choose for the pipe
For…TransducerRange and temperature
General purpose5 MHz · Ø10 mm1 – 300 mm
-10 to 40 °C
Thin walls and small diameters7 MHz · Ø6 mm0.8 – 70 mm
-10 to 40 °C
Thick walls or attenuating materials2 MHz · Ø12 o Ø22 mm4 – 500 mm
-10 to 40 °C
Hot pipes5 MHz · Ø10 mm, alta temperatura1 – 250 mm
up to 150 or 350 °C
Painted pipes (echo-echo, QS5 DLE)5 MHz · Ø10 mm Hi-Damp2.5 – 25 mm under paint
-10 to 70 °C

On small-diameter pipes, the smaller the transducer face, the better it sits on the curve. For walls below the transducer's minimum, see the "doubling" mistake below.

dmq high-temperature transducer up to 350 degrees
High-temperature transducer, up to 350 °C, to measure in-service pipes without shutting them down.

Sources: DEMEQ, QS5 user manual (B-Scan, material condition analyser, alarms, memory) and QS transducer specifications published by DEMEQ.

Other common mistakes

Trusting a reading that is too high on a heavily corroded area

If the wall has dropped below the transducer's minimum thickness, the gauge may show double (or even triple) the real thickness: this is the "doubling" effect. When a reading doesn't match what you see, check with a lower-range transducer, such as the 7 MHz one.

Measuring a hot pipe with a cold calibration

Temperature changes the sound velocity in the steel and in the transducer. Use a high-temperature transducer and calibrate at the pipe temperature.

Measuring a painted pipe in pulse-echo

The paint adds to the reading, with an error larger than its own thickness, and can hide wall loss. Measure in echo-echo with the QS5 DLE or on an unpainted spot.

Pipe in production, not in service? For measuring wall thickness in line, during extrusion, it's a different instrument: the QST multichannel gauge. See the guide pipe wall thickness during production.

The instrument for corrosion inspection

The QS5 has the tools to map corrosion. The QS3, to check thickness on a tighter budget.

Other guides

If your question is a different one, it may already be answered in one of these. View all guides

Measuring thickness through paint

The QS5 DLE echo-echo mode: the steel without grinding or repainting.

Read the guide

Ultrasonic velocity by material

Velocity chart and why a wrong value becomes a thickness error.

Read the guide

Hall effect or ultrasound

How to measure wall thickness depending on the material, the thickness and access to the part.

Read the guide

Which pipework do you need to inspect?

Tell us the material, diameter and nominal thickness, whether it is painted or hot and how often you inspect it. We'll confirm the model and transducers that fit.

Josep QuerolTechnical and sales lead

Or directly: +34 623 790 365 · info (at) vqndt.com

WhatsApp